VSR-S (1)

POTTER VSR-S Water Flow Switch 1″-2” Threaded Brass w/Retard

Water Flow Alarm Switch for Small Pipes

Technical Data
Approvals 03 Service Pressure 300 PSI (20,68 BAR) - UL Flow Required for Alarm 10 GPM (38 LPM) Maximum Surge 18 FPS (5,5 m/s) Enclosure Die-cast, red powdercoat finish Contact Ratings Two sets of SPDT (Form C) 10.0 Amps at 125/250VAC 2.0 Amps at 30VDC Resistive 10 m Amps min. at 24VDC Conduit Entrances Two 1/2" conduit connections provided. Individual switch compartments suitable for dissimilar voltages  WARNING: Cancer and Reproductive Harm www.P65Warnings.ca.gov